156 ACS550-01/U1 User’s Manual
Parameters
For other faults, or for anticipating motor overheating using a model, see Group 30:
FAULT FUNCTIONS.
Code Description
3501 SENSOR TYPE
Identifies the type of the motor temperature sensor used, PT100 (°C), PTC (ohm) or thermistor.
See parameters 1501
AO1 CONTENT SEL and 1507 AO2 CONTENT SEL.
0 =
NONE
1 = 1 x PT100 – Sensor configuration uses one PT100 sensor.
• Analog output
AO1 or AO2 feeds constant current through the sensor.
• The sensor resistance increases as the motor temperature rises, as does the voltage over the sensor.
• The temperature measurement function reads the voltage through analog input AI1 or AI2 and converts it to
degrees Celsius.
2 = 2 x PT100 – Sensor configuration uses two PT100 sensors.
• Operation is the same as for above 1 x PT100.
3 = 3 x PT100 – Sensor configuration uses three PT100 sensors.
• Operation is the same as for above 1 x PT100.
4 =
PTC – Sensor configuration uses one PTC.
• The analog output feeds a constant current through the sensor.
• The resistance of the sensor increases sharply as the motor
temperature rises over the PTC reference temperature (T
ref
), as
does the voltage over the resistor. The temperature measurement
function reads the voltage through analog input AI1 and converts it
into ohms.
• The table below and the graph show typical PTC sensor resistance
as a function of the motor operating temperature.
5 =
THERM(0) – Sensor configuration uses a thermistor.
Motor thermal protection is activated through a digital input. Connect
either a PTC sensor or a normally closed thermistor relay to a digital
input.
• When the digital input is ‘0’, the motor is overheated.
• See the connection figure on page 155.
• The table below and the graph show the resistance requirements for a PTC sensor connected between 24 V and
a digital input as a function of the motor operating temperature.
6 =
THERM(1) – Sensor configuration uses a thermistor.
• Motor thermal protection is activated through a digital input. Connect a normally open thermistor relay to a digital
input.
• When the digital input is ‘1’, the motor is overheated.
• See the connection figure on page 155.
3502 INPUT SELECTION
Defines the input used for the temperature sensor.
1 =
AI1 – PT100 and PTC.
2 =
AI2 – PT100 and PTC.
3…8 =
DI1…DI6 – Thermistor and PTC
3503 ALARM LIMIT
Defines the alarm limit for motor temperature measurement.
At motor temperatures above this limit, the drive displays an alarm (2010, MOTOR TEMP)
For thermistors or PTC connected to a digital input:
0 – de-activated
1 – activated
T
Excessive
Normal
Temperature Resistance
Normal < 1.5 kohm
Excessive > 4 kohm
Temperature Resistance
Normal < 3 kohm
Excessive > 28 kohm