54 ACS550-01/U1 User’s Manual
Control panels
The table below lists the tasks of the assistants and the relevant drive parameters.
Depending on the selection made in the Application task (parameter 9902 APPLIC
MACRO), the Start-up Assistant decides, which consequent tasks it suggests.
5. • To accept the new value and continue to the setting of the next parameter,
press .
• To stop the assistant, press .
Name Description Set parameters
Language select Selecting the language 9901
Motor set-up Setting the motor data
Performing the motor identification. (If the speed limits are not in
the allowed range: Setting the limits.)
99049909
9910
Application Selecting the application macro 9902, parameters associated to
the macro
Option modules Activating the option modules Group 35: MOTOR TEMP MEAS
Group 52: PANEL COMM
9802
Speed control
EXT1
Selecting the source for the speed reference 1103
(If AI1 is used: Setting analog input AI1 limits, scale, inversion) (13011303, 3001)
Setting the reference limits 1104, 1105
Setting the speed (frequency) limits 2001, 2002, (2007, 2008)
Setting the acceleration and deceleration times 2202, 2203
Speed control
EXT2
Selecting the source for the speed reference 1106
(If AI1 is used: Setting analog input AI1 limits, scale, inversion) (13011303, 3001)
Setting the reference limits 1107, 1108
Torque control Selecting the source for the torque reference 1106
(If AI1 is used: Setting analog input AI1 limits, scale, inversion) (13011303, 3001)
Setting the reference limits 1107, 1108
Setting the torque ramp up and ramp down times 2401, 2402
PID control Selecting the source for the process reference 1106
(If AI1 is used: Setting analog input AI1 limits, scale, inversion) (13011303
, 3001)
Setting the reference limits 1107, 1108
Setting the speed (reference) limits 2001, 2002, (2007, 2008)
Setting the source and limits for the process actual value 4016, 4018, 4019
Start/Stop control Selecting the source for start and stop signals of the two external
control locations, EXT1 and EXT2
1001, 1002
Selecting between EXT1 and EXT2 1102
Defining the direction control 1003
Defining the start and stop modes 21012103
Selecting the use of Run Enable signal 1601
Timed functions Setting the timed functions Group 36: TIMED FUNCTIONS
Selecting the timed start/stop control for external control locations
EXT1 and EXT2
1001, 1002
Selecting timed EXT1/EXT2 control 1102
Activation of timed constant speed 1 1201
Step Action Display
SAVE
EXIT
9906 MOTOR NOM CURR
PAR EDIT
1.2 A
EXIT SAVE
00:00
LOC