Table 11. The Status Word for the ABB Drives communication
profile. The upper case boldface text refers to the states shown in
Figure 12.
Bit Name Value STATE/Description
0 RDY_ON 1 READY TO SWITCH ON.
0 NOT READY TO SWITCH ON.
1 RDY_RUN 1 READY TO OPERATE.
0 OFF1 ACTIVE.
2 RDY_REF 1 OPERATION ENABLED.
0 OPERATION INHIBITED.
3 TRIPPED 1 FAULT.
0 No fault.
4 OFF_2_STA 1 OFF2 inactive.
0 OFF2 ACTIVE.
5 OFF_3_STA 1 OFF3 inactive.
0 OFF3 ACTIVE.
6SWC_ON_
INHIB
1 SWITCH-ON INHIBITED.
0–
7 ALARM 1 Warning/Alarm.
0 No warning/alarm.
8AT_
SETPOINT
1 OPERATING. Actual value equals reference = is
within tolerance limits, i.e. in speed control, speed
error is 10% max. of nominal motor speed.
0 Actual value differs from reference = is outside
tolerance limits.
9 REMOTE 1 Drive control location: REMOTE (EXT1 or EXT2).
0 Drive control location: LOCAL.