1-164 ACH550-UH User’s Manual
Parameters
Group 51: EXT COMM MODULE
This group defines set-up variables for a fieldbus adapter (FBA) communication
module. For more information on these parameters, refer to the user’s manual
supplied with the FBA module.
Group 51: Ext Comm Module
Code Description Range Resolution Default S
5101 FBA TYPE 0000...FFFF hex - 0000 hex (
NOT DEFINED)
Displays the type of the connected fieldbus adapter module.
0000 =
NOT DEFINED – Module not found, or not properly connected, or parameter 9802 is not set to 4 (EXT FBA).
0001 =
PROFIBUS-DP
0015 = LONWORKS
0020 = CANopen
0025 = DEVICENET
0065 = CONTROLNET
0080 = ETHERNET
5102
5126
FB PAR 2…FB PAR 26 0...65535 1 0
Refer to communication module documentation for more information on these parameters.
5127 FBA PAR REFRESH 0, 1 1 0 (
DONE)
Validates any changed fieldbus parameter settings.
0 =
DONE – Refreshing done.
1 =
REFRESH – Refreshing.
After refreshing, the value reverts automatically to
DONE.
5128 FILE CPI FW REV 0000…FFFF hex 1 0000 hex
Displays the CPI firmware revision of the drive’s fieldbus adapter configuration file. Format is 0xyz where:
x = major revision number
y = minor revision number
z = correction number
Example: 0107 = revision 1.07
5129 FILE CONFIG ID 0000…FFFF hex 1 0000 hex
Displays the revision of the drive’s fieldbus adapter module’s configuration file identification.
File configuration information is drive application program-dependent.
5130 FILE CONFIG REV 0000…FFFF hex 1 0000 hex
Contains the revision of the drive’s fieldbus adapter module configuration file.
Example: 0001 = revision 1
5131 FBA STATUS 0…6 1 0 (
IDLE)
Contains the status of the adapter module.
0 =
IDLE Adapter not configured.
1 =
EXECUT INIT – Adapter is initializing.
2 =
TIME OUT – A timeout has occurred in the communication between the adapter and the drive.
3 = CONFIG ERROR – Adapter configuration error.
• The revision code of the adapter’s CPI firmware revision is older than required CPI firmware version defined in
the drive’s configuration file (parameter 5132 < 5128).
4 =
OFF-LINE – Adapter is off-line.
5 =
ON-LINE – Adapter is on-line.
6 =
RESET – Adapter is performing a hardware reset.
5132 FBA CPI FW REV 0000…FFFF hex 1 0000 hex
Contains the revision of the module’s CPI program. Format is 0xyz where:
x = major revision number
y = minor revision number
z = correction number
Example: 0107 = revision 1.07
Vue de la page 167