ABB RDNA-01 Manuel d'utilisateur Page 184

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 348
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 183
1-180 ACH550-UH User’s Manual
Parameters
3 = DI3 – Enables the Interlocks function and assigns a digital input (starting with DI3) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFA)]
• the Autochange function status (disabled if 8118
AUTOCHNG INTERV = 0.0, and otherwise enabled).
4 =
DI4 – Enables the Interlock function and assigns a digital input (starting with DI4) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFA)]
• the Autochange function status (disabled if 8118
AUTOCHNG INTERV = 0.0, and otherwise enabled).
Group 81: PFA Control
Code Description Range Resolution Default S
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1…DI2: Free
DI3: Speed Reg Motor
DI4…DI6: Free
Not allowed
1
DI1…DI2: Free
DI3: Speed Reg Motor
DI4: First PFA Relay
DI5…DI6: Free
DI1…DI2: Free
DI3: First PFA Relay
DI4…DI6: Free
2
DI1…DI2: Free
DI3: Speed Reg Motor
DI4: First PFA Relay
DI5: Second PFA Relay
DI6: Free
DI1…DI2: Free
DI3: First PFA Relay
DI4: Second PFA Relay
DI5…DI6: Free
3
DI1…DI2: Free
DI3: Speed Reg Motor
DI4: First PFA Relay
DI5: Second PFA Relay
DI6: Third PFA Relay
DI1…DI2: Free
DI3: First PFA Relay
DI4: Second PFA Relay
DI5: Third PFA Relay
DI6: Free
4Not allowed DI1…DI2: Free
DI3: First PFA Relay
DI4: Second PFA Relay
DI5: Third PFA Relay
DI6: Fourth PFA Relay
5…6 Not allowed Not allowed
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1…DI3: Free
DI4: Speed Reg Motor
DI5…DI6: Free
Not allowed
1
DI1…DI3: Free
DI4: Speed Reg Motor
DI5: First PFA Relay
DI6: Free
DI1…DI3: Free
DI4: First PFA Relay
DI5…DI6: Free
2
DI1…DI3: Free
DI4: Speed Reg Motor
DI5: First PFA Relay
DI6: Second PFA Relay
DI1…DI3: Free
DI4: First PFA Relay
DI5: Second PFA Relay
DI6: Free
3 Not allowed
DI1…DI3: Free
DI4: First PFA Relay
DI5: Second PFA Relay
DI6: Third PFA Relay
4…6 Not allowed Not allowed
Vue de la page 183
1 2 ... 179 180 181 182 183 184 185 186 187 188 189 ... 347 348

Commentaires sur ces manuels

Pas de commentaire