Parameter listing and descriptions 311
ACH550-01 User's Manual
8120 INTERLOCKS 0…6
Defines operation of the Interlock function. When the Interlock function
is enabled:
An interlock is active when its command signal is absent.
An interlock is inactive when its command signal is present.
The ACH550 will not start if a start command occurs when the speed
regulated motor’s interlock is active – the control panel displays an
alarm (2015,
PFA I LOCK).
Wire each Interlock circuit as follows:
Wire a contact of the motor’s On/Off switch to the Interlock circuit
the drive’s PFA logic can then recognise that the motor is switched off
and start the next available motor.
Wire a contact of the motor thermal relay (or other protective device in
the motor circuit) to the Interlock input – the drive’s PFA logic can then
recognise that a motor fault is activated and stop the motor.
0 =
NOT SEL – Disables the Interlock function. All digital inputs are
available for other purposes.
• Requires 8118
AUTOCHNG INTERV = 0.0 (The Autochange function
must be disabled if Interlock function is disabled.)