ABB RCNA-01 Manuel d'utilisateur Page 34

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 474
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 33
30 Preparing for installation
ACH550-01 User's Manual
Effective motor cable shields
The general rule for cable shield effectiveness is: the better and
tighter the shield, the lower the radiated emission level. The
figure below shows an example of an effective construction (for
example Ölflex-Servo-FD 780 CP, Lapp Kabel or MCCMK,
Draka NK Cables).
Clamp the cable shield into the gland plate at the drive end, twist
the cable shield wires together into a bundle (pigtail) not longer
than five times its width and connect it to the terminal marked
(at the bottom right-hand corner of the drive) if you are using
a cable without a separate PE conductor.
Insulation jacket
Braided metallic shield
Inner insulator
L1
L2
L3
Vue de la page 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 473 474

Commentaires sur ces manuels

Pas de commentaire