ABB RCNA-01 Manuel d'utilisateur Page 405

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 474
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 404
Technical data 401
ACH550-01 User's Manual
Note 1: Mains cable sizing is based on a correction factor of 0.71
(maximum of 4 cables laid on a cable ladder side by side, ambient
temperature 30 °C (86 °F), EN 60204-1 and IEC 364-5-523). For other
conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive. In any case, the
cable must be between the minimum limit defined in this table and the
maximum limit defined by the terminal size (see section Input power and
motor connection terminals on page 402.)
186 3x95 285 2x
(3x95)
178 2/0
215 3x120 205 3/0
249 3x150 237 4/0
284 3x185 264 250 MCM or
2 x 1
330 3x240 291 300 MCM or
2 x 1/0
319 350 MCM or
2 x 2/0
IEC NEC
Based on:
EN 60204-1 and IEC 60364-5-2/2001
PVC insulation
30 °C (86 °F) ambient temperature
70 °C (158 °F) surface temperature
cables with concentric copper shield
not more than nine cables laid on cable
ladder side by side.
Based on:
NEC Table 310-16 for copper
wires
90 °C (194 °F) wire insulation
40 °C (104 °F) ambient
temperature
not more than three current-
carrying conductors in
raceway or cable, or earth
(directly buried)
copper cables with
concentric copper shield.
Max
load
current
A
Cu
cable
mm
2
Max
load
current
A
Al cable
mm
2
Max load
current
A
Cu wire size
AWG/kcmil
Vue de la page 404
1 2 ... 400 401 402 403 404 405 406 407 408 409 410 ... 473 474

Commentaires sur ces manuels

Pas de commentaire