Parameter listing and descriptions 321
ACH550-01 User's Manual
Group 98: OPTIONS
This group configures for options, in particular, enabling serial
communication with the drive.
Code Description Range
9802 COMM PROT SEL 0…5
Selects the communication protocol.
0 =
NOT SEL – No communication protocol selected.
1 =
STD MODBUS – The drive communicates via a Modbus controller via
the RS485 serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
2 =
N2 – The drive communicates via an N2 controller via the RS485
serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
3 = FLN – The drive communicates via an FLN controller via the RS485
serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
4 =
EXT FBA – The drive communicates via a fieldbus adapter module in
option slot 2 of the drive.
• See also parameter Group 51: EXT COMM MODULE.
5 =
BACNET – The drive communicates via a BACnet controller via the
RS485 serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.