Parameter listing and descriptions 195
ACH550-01 User's Manual
Group 14: RELAY OUTPUTS
This group defines the condition that activates each of the relay
outputs.
Code Description Range
1401 RELAY OUTPUT 1 0…47
Defines the event or condition that activates relay 1 – what relay output
1 means.
0 =
NOT SEL – Relay is not used and is de-energised.
1 =
READY – Energise the relay when the drive is ready to function.
Requires:
• Run enable signal is present.
• No faults exist.
• Supply voltage is within range.
• Emergency Stop command is not on.
2 =
RUN – Energise the relay when the drive is running.
3 =
FAULT(-1) – Energise the relay when power is applied. De-energise
when a fault occurs.
4 =
FAULT – Energise the relay when a fault is active.
5 =
ALARM – Energise the relay when an alarm is active.
6 =
REVERSED – Energise the relay when the motor rotates in reverse
direction.
7 =
STARTED – Energise the relay when the drive receives a start
command (even if Run enable signal is not present). De-energise the
relay when the drive receives a stop command or a fault occurs.
8=
SUPRV1 OVER – Energise the relay when the first supervised
parameter (3201) exceeds the limit (3203).
•See Group 32: SUPERVISION.
9 =
SUPRV1 UNDER – Energise the relay when the first supervised
parameter (3201) drops below the limit (3202).
•See Group 32: SUPERVISION.
10 =
SUPRV2 OVER – Energise the relay when the second supervised
parameter (3204) exceeds the limit (3206).
•See Group 32: SUPERVISION.
11 =
SUPRV2 UNDER – Energise the relay when the second supervised
parameter (3204) drops below the limit (3205).
•See Group 32: SUPERVISION.
12 =
SUPRV3 OVER – Energise the relay when the third supervised
parameter (3207) exceeds the limit (3209).
•See Group 32: SUPERVISION.
13 =
SUPRV3 UNDER – Energise the relay when the third supervised
parameter (3207) drops below the limit (3208).
•See Group 32: SUPERVISION.