Diagnostics and maintenance 373
ACH550-01 User's Manual
1012
PAR PFA IO 1 IO configuration is not complete – not
enough relays are parameterized for PFA.
Or, a conflict exists between group 14,
parameter 8117
NR OF AUX MOT and
parameter 8118
AUTOCHNG INTERV.
1013
PAR PFA IO 2 IO configuration is not complete – the actual
number of PFA motors (parameter 8127
MOTORS) does not match the PFA motors in
group 14 and parameter 8118
AUTOCHNG
INTERV.
1014
PAR PFA IO 3 IO configuration is not complete – the drive
is unable to allocate a digital input (interlock)
for each PFA motor (parameters 8120
INTERLOCKS and 8127 MOTORS).
1015
RESERVED Not used.
1016
PAR USER LOAD
C
Parameter values for the user load curve are
inconsistent. Check that the following
conditions are met:
•3704LOAD FREQ 1 < 3707 LOAD FREQ 2 <
3710
LOAD FREQ 3 <
3713
LOAD FREQ 4 < 3716 LOAD FREQ 5.
•3705LOAD TORQ LOW 1 < 3706 LOAD TORQ
HIGH 1.
•3708LOAD TORQ LOW 2 < 3709 LOAD TORQ
HIGH 2.
•3711
LOAD TORQ LOW 3 < 3712 LOAD TORQ
HIGH 3.
•3714LOAD TORQ LOW 4 < 3715 LOAD TORQ
HIGH 4.
•3717LOAD TORQ LOW 5 < 3718 LOAD TORQ
HIGH 5.
-
UNKNOWN DRIVE
TYPE: ACH550
SUPPORTED
DRIVES: X
Wrong type of panel, i.e. panel that supports
drive X but not the ACH550, has been
connected to the ACH550.
Fault
code
Fault name in
the panel
Description and
recommended corrective action