Fieldbus control description
18
When torque or speed reference scaling is selected (by parameter 50.04 FBA REF1
MODESEL / 50.05 FBA REF2 MODESEL), the fieldbus references are 32-bit
integers. The value consists of a 16-bit integer value and a 16-bit fractional value.
The speed/torque reference scaling is as follows:
Reference Scaling Notes
Torque reference FBA REF / 65536
(value in%)
Final reference is limited by parameters 20.06 MAXIMUM
TORQUE and 20.07 MINIMUM TORQUE.
Speed reference FBA REF / 65536
(value in rpm)
Final reference is limited by parameters 20.01 MAXIMUM
SPEED, 20.02 MINIMUM SPEED and 24.12 SPEED
REFMIN ABS.
Position reference
See parameter group 60 POS FEEDBACK.
Velocity reference