Starting up the FPBA-01 adapter for different communication profiles
27
*Read-only or automatically detected/set
Note: By default, fieldbus is not the only control source. See actual signal 2.12 FBA MAIN CW in
ACSM1 Motion Control Program Firmware Manual for details.
The position setpoint is scaled as follows:
**Example
The position setpoint and actual values are scaled with the above example values as
follows:
Example for velocity setpoint scale:
**Example
51.05 PROFILE 4 (= PROFIdrive
Positioning)
Control Word according to the PROFIdrive
Positioning mode
52.01 FBA DATA IN1 4* Status Word
52.02 FBA DATA IN2 15 Actual value 1
52.04 FBA DATA IN4 16 Actual value 2
53.01 FBA DATA OUT2 1* Control Word
53.02 FBA DATA OUT2 12 Reference 1
53.04 FBA DATA OUT4 13 Reference 2
51.27 FBA PAR REFRESH REFRESH Refreshing parameter settings of the
module
Drive parameter Setting
60.05 POS UNIT (Position unit) m**
60.08 POS2INT SCALE 100**
Drive
parameter
Name Value Description
60.10 POS SPEED UNIT u/s** Unit/s (in this case m/s)
60.11 POS SPEED2INT 100** Scales position speed values to integer values.
Selections: 1/10/100/1000/10000/100000
1000 / 100 = 10.00 m
60.05 POS UNIT
Physical value
60.08 POS2INT SCALE
Setpoint value