144 Serial communications
ACH550-01 User's Manual
The new settings will take effect when the drive is next powered
up, or when parameter 5127 is activated.
Protocol selection
FBA communication parameters
4 Select EXT FBA with the
UP/DOWN keys and press
SAVE.
5 The assistant recognises
the type of the connected
fieldbus adapter module
and guides you through the
necessary set-up.
If the name of FBA
parameter is not self-
explanatory, the assistant
first tells you which
information is expected
from you.
Code Description Range
9802 COMM PROT SEL 0…5
Selects the communication protocol.
0 =
NOT SEL – No communication protocol selected.
4 =
EXT FBA – The drive communicates via a fieldbus adapter module in
option slot 2 of the drive.
• See also parameter Group 51: EXT COMM MODULE.
Code Description Range
5101 FBA TYPE
Displays the type of the connected fieldbus adapter module.
0 =
NOT
DEFINED
– Module not found or not connected. Check chapter
Mechanical installation in the fieldbus user’s manual and check that
parameter 9802 is set to 4 = EXT FBA.
1 =
Profibus-DP
21 = LonWorks
32 = CANopen
37 = DeviceNet
101 = ControlNet
128 = Ethernet
132 = PROFINET
136 =
EPL - Ethernet POWERLINK
144 = CC-Link
9802 COMM PROT SEL
PAR EDIT
EXT FBA
[4]
OFF
EXIT SAVE
00:00
On next screen
set the node number.
EXIT
OK
00:00
ASSISTANT
OFF
5102 FBA PAR 2
PAR EDIT
3
OFF
EXIT SAVE00:00