Parameter listing and descriptions 291
ACH550-01 User's Manual
5207 BUFFER OVERRUNS 0…65535
Contains a count of the characters received that cannot be placed in the
buffer.
Longest possible message length for the drive is 128 bytes.
Received messages exceeding 128 bytes overflow the buffer. The
excess characters are counted.
5208 CRC ERRORS 0…65535
Contains a count of the messages with a CRC error that the drive
receives. For high counts, check:
Ambient electro-magnetic noise levels – high noise levels generate
errors.
•CRC calculations for possible errors.