ABB RCNA-01 Manuel d'utilisateur Page 284

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 474
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 283
280 Parameter listing and descriptions
ACH550-01 User's Manual
4021 ACT2 MAXIMUM -1000…1000%
Sets the maximum value for
ACT2.
See 4018
ACT1 MINIMUM.
4022 SLEEP SELECTION -6…7
Defines the control for the PID sleep function.
0 =
NOT SEL– Disables the PID sleep control function.
1 =
DI1 – Defines digital input DI1 as the control for the PID sleep
function.
• Activating the digital input activates the sleep function.
• De-activating the digital input restores PID control.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for the
PID sleep function.
•See
DI1 above.
7 =
INTERNAL – Defines the output rpm/frequency, process reference,
and process actual value as the control for the PID sleep function.
• Refer to parameters 4025
WAKE-UP DEV and 4023 PID SLEEP LEVEL.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for the
PID sleep function.
• De-activating the digital input activates the sleep function.
• Activating the digital input restores PID control.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the control for the PID sleep function.
•See
DI1(INV) above.
Code Description Range
Vue de la page 283
1 2 ... 279 280 281 282 283 284 285 286 287 288 289 ... 473 474

Commentaires sur ces manuels

Pas de commentaire