Parameter listing and descriptions 303
ACH550-01 User's Manual
8113 LOW FREQ 2 0.0…500 Hz
Sets the frequency limit used to stop the second auxiliary motor.
See 8112
LOW FREQ 1 for a complete description of the operation.
The second auxiliary motor stops if:
two auxiliary motors are running.
ACH550 output frequency drops below the limit 8113 - 1.
output frequency stays below the relaxed limit (8113 + 1 Hz) for at
least the time 8116
AUX MOT STOP D.
8114 LOW FREQ 3 0.0…500 Hz
Sets the frequency limit used to stop the third auxiliary motor.
See 8112
LOW FREQ 1 for a complete description of the operation.
The third auxiliary motor stops if:
three auxiliary motors are running.
ACH550 output frequency drops below the limit: 8114 - 1.
output frequency stays below the relaxed limit (8114 + 1 Hz) for at
least the time 8116
AUX MOT STOP D.
8115 AUX MOT START D 0.0…3600 s
Sets the Start Delay for the auxiliary motors.
The output frequency must remain above the start frequency limit
(parameter 8109, 8110 or 8111) for this time period before the
auxiliary motor starts.
•See 8109
START FREQ 1 for a complete description of the operation.
8116 AUX MOT STOP D 0.0…3600 s
Sets the Stop Delay for the auxiliary motors.
The output frequency must remain below the low frequency limit
(parameter 8112, 8113 or 8114) for this time period before the
auxiliary motor stops.
See 8112
LOW FREQ 1 for a complete description of the operation.